Indoor Air Change Exponential Removal Term Tool

Ideal well-mixed removal toward a supplied equilibrium concentration.

Loading tool…

Description

Compute remainingFraction = exp(-airChangesPerHour*hours) and finalConcentration = equilibrium+(initial-equilibrium)*remainingFraction.

Air-change and transfer calculations relate a volume, flow, time and driving force under an assumed model. Nominal air exchange or a well-mixed exponential response differs from measured clearance, spatial mixing and contaminant-specific treatment.

Compute remainingFraction = exp(-airChangesPerHour*hours) and finalConcentration = equilibrium+(initial-equilibrium)*remainingFraction.

When to use this tool

Use Indoor Air Change Exponential Removal Term when checking a supplied ventilation, concentration-decay or oxygen-transfer term.

How to use the tool and how it works

  1. Enter initial, equilibrium, airChangesPerHour, hours. Use the units and conventions below.
  2. Run the tool. Correct any format, range, or cross-field input error before interpreting the output.
  3. Read remainingFraction, finalConcentration. Use the output convention below.

Require nonnegative initial, equilibrium, airChangesPerHour and hours. Compute remainingFraction = exp(-airChangesPerHour*hours) and finalConcentration = equilibrium+(initial-equilibrium)*remainingFraction. Concentrations share one unit and time is in hours; remainingFraction is the fraction of the initial departure from equilibrium.1

The well-mixed air-removal model relates concentration ratios exponentially to air changes and time. The zero-equilibrium case here has that form; the supplied equilibrium term is an additional constant-reference assumption.2

Input fieldMeaning and unitsAccepted input
initialInitialRequired. Finite number; minimum 0.
equilibriumEquilibriumRequired. Finite number; minimum 0.
airChangesPerHourAir Changes Per HourRequired. Finite number; minimum 0.
hoursHoursRequired. Finite number; minimum 0.
Output fieldInterpretationReturned shape
remainingFractionFraction of initial departure from equilibrium retained, exp(-ACH*hours).Required. Finite number.
finalConcentrationFinal ConcentrationRequired. Finite number.
json
{
  "input": {
    "initial": 100,
    "equilibrium": 10,
    "airChangesPerHour": 2,
    "hours": 0.5
  },
  "output": {
    "remainingFraction": 0.36787944117144233,
    "finalConcentration": 43.10914970542981
  }
}

Limitations and assumptions

  • This assumes constant effective removal rate, constant equilibrium and complete mixing. Concentration rises when initial is below equilibrium; the fraction is not always final/initial. Ongoing variable sources, stagnant zones and infection risk are not modeled.
  • Inputs must satisfy both the field types and the cross-field conditions above. Invalid input causes an error; a successful false flag or documented placeholder is a different result.
  • Numeric calculations use binary floating point unless exact decimal-integer arithmetic is explicitly stated. No hidden measurement tolerance or decimal rounding is added; nonfinite or out-of-contract results are rejected. Numeric signed-zero results are exported as zero.

Alternative or Complementary methods

Use measured effective airflow and a suitable mixing or transport model before drawing conclusions about treatment performance or exposure.

References

  1. Calculation and input contract: environmental-health/indoor-air-change-exponential-removal-term — tool.io

  2. Appendix B: airborne contaminant removal — Centers for Disease Control and Prevention